407
Analog Output Units Section 7-3
When the resolution is 1/12,000, the hexadecimal values 0000 to 2EE0 (0 to
12000) correspond to an analog voltage range of 0 to 10 V.
The entire output range is –0.5 to 10.5 V.
Specify a negative voltage as a two’s complement.
1 to 5 V
When the resolution is 1/6,000, the hexadecimal values 0000 to 1770 (0 to
6000) correspond to an analog voltage range of 1 to 5 V.
The entire output range is 0.8 to 5.2 V.
When the resolution is 1/12,000, the hexadecimal values 0000 to 2EE0 (0 to
12000) correspond to an analog voltage range of 1 to 5 V.
The entire output range is 0.8 to 5.2 V.
0 to 20 mA
When the resolution is 1/6,000, the hexadecimal values 0000 to 1770 (0 to
6000) correspond to an analog current range of 0 to 20 mA.
The entire output range is 0 to 21 mA.
0 V
10 V
10.5 V
0.5 V
FED4
(300)
189C
(6300)
1770
(6000)
8000
7FFF
0000 (0)
Conversion
Data
Hexadecimal
(Decimal)
0 V
10 V
10.5 V
0.5 V
FDA8
(600)
3138
(12600)
2EE0
(12000)
0000 (0)
8000
7FFF
Conversion Data
Hexadecimal (Decimal)
1 V
5 V
5.2 V
0.8 V
189C
(6300)
1770
(6000)
0 V
7FFF
FED4
(300)
8000
Conversion
Data
Hexadecimal
(Decimal)
1 V
5 V
5.2 V
0.8 V
3138
(12600)
2EE0
(12000)
0 V
7FFFFDA8
(600)
8000
Conversion Data