408
Analog Output Units Section 7-3
When the resolution is 1/12,000, the hexadecimal values 0000 to 2EE0 (0 to
12000) correspond to an analog voltage range of 0 to 20 mA.
The entire output range is 0 to 21 mA.
4 to 20 mA
When the resolution is 1/6,000, the hexadecimal values 0000 to 1770 (0 to
6000) correspond to an analog current range of 4 to 20 mA.
The entire output range is 3.2 to 20.8 mA.
When the resolution is 1/12,000, the hexadecimal values 0000 to 2EE0 (0 to
12000) correspond to an analog voltage range of 4 to 20 mA.
The entire output range is 3.2 to 20.8 mA.
Conversion
Data
Hexadecimal
(Decimal)
0 mA
20 mA
21 mA
189C
(6300)
1770
(6000)
7FFF
8000
0000 (0)
0 mA
20 mA
21 mA
0000 (0)
3138
(12600)
2EE0
(12000)
7FFF
8000
Conversion Data
Hexadecimal (Decimal)
Conversion
Data
Hexadecimal
(Decimal)
4 mA
20 mA
20.8 mA
3.2 mA
189C
(6300)
1770
(6000)
0 mA
7FFF
FED4
(300)
8000
4 mA
20 mA
20.8 mA
3.2 mA
3138
(12600)
2EE0
(12000)
0 mA
7FFF
FDA8
(600)
8000
Conversion Data
Hexadecimal (Decimal)