442
Analog I/O Units Section 7-4
CP1W-MAD44
Analog
input
Input
range
Range
code
Averaging Set data Destination
word
Input 1 4 to 20 mA 10 Yes 1110 (E hex) n+1
Input 2 0 to 10 V 01 No 1001 (9 hex) n+1
Input 3 0 to 5 V 11 Yes 1111 (F hex) n+2
Input 4 −10 to 10 V 00 Yes 1100 (C hex) n+2
Output 1 −10 to 10 V 000 --- 1000 (8 hex) n+3
Output 2 4 to 20 mA 100 --- 1100 (C hex) n+3
Output 3 0 to 10 V 001 --- 1001 (9 hex) n+4
Output 4 Not use --- --- 0000 (0 hex) n+4
MOV(021)
#88DE
102
First Cycle Flag
A200.11
A200.11
A200.11
A200.11
A200.11
A200.11
#8CCF
MOV(021)
103
#809E
104
MOV(021)
#80CF
105
MOV(021)
#80C8
106
MOV(021)
#8009
107
MOV(021)
← Writes the range code of CP1W-MAD42 to the Unit.
← Writes the range code of CP1W-MAD44 to the Unit.