463
Temperature Sensor Units Section 7-5
Analog Input Signal
Ranges
When the input exceeds the specified range, the AD converted data will be
fixed at either the lower limit or upper limit.
0 to 10 V
The 0 to 10 V range corresponds to the hexadecimal values 0000 to 2EE0 (0
to 12000). The entire data range is FDA8 to 3138 (600 to 12600). A negative
voltage is expressed as a two’s complement.
1 to 5 V
The 1 to 5 V range corresponds to the hexadecimal values 0000 to 2EE0 (0 to
12000). The entire data range is FDA8 to 3138 (600 to 12600). Inputs
between 0.8 and 1 V are expressed as two’s complements. If the input falls
below 0.8 V, open-circuit detection will activate and converted data will be
8000.
4 to 20 mA
The 4 to 20 mA range corresponds to the hexadecimal values 0000 to 2EE0
(0 to 12000). The entire data range is FDA8 to 3138 (600 to 12600). Inputs
between 3.2 and 4 mA are expressed as two’s complements. If the input falls
below 3.2 mA, open-circuit detection will activate and converted data will be
8000.
0 V 10 V
10.5 V
0.5 V
FDA8 (600)
3138 (12600)
2EE0 (12000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
1 V 5 V
5.2 V
0.8 V
FDA8 (600)
3138 (12600)
2EE0 (12000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
4 mA 20 mA
20.8 mA
3.2 mA
FDA8 (600)
3138 (12600)
2EE0 (12000)
0000 (0)
0 mA
Converted Data
Hexadecimal (Decimal)