464
Temperature Sensor Units Section 7-5
Open-circuit Detection
Function for Temperature
If the circuit is disconnected, the open-circuit detection function will operate
and the converted temperature data will be set to 7FFF.
Open-circuit Detection
Function for Analog
Inputs
The open-circuit detection function is activated when the input range is set to
1 to 5 V and the voltage drops below 0.8 V, or when the input range is set to 4
to 20 mA and the current drops below 3.2 mA. When the open-circuit detec-
tion function is activated, the converted data will be set to 8,000.
The time for enabling or clearing the open-circuit detection function is the
same as the time for converting the data. If the input returns to the convertible
range, the open-circuit detection is cleared automatically and the output
returns to the normal range.
Creating a Ladder
Program
Word Allocations
Temperature Sensor Units are allocated words in the same way as other CP-
series Expansion Units or Expansion I/O Units, in order of connection. A Tem-
perature Sensor Unit is allocated the next input words following the input
words of the CPU Unit or previous Expansion Unit or Expansion I/O Unit. Four
input words are allocated to CP1W-TS003.
Example
Converted Temperature Data
The converted temperature value will be stored in the input words allocated to
the Temperature Sensor Unit in 4-digit hexadecimal.
“m” is the last input word allocated to the CPU Unit, Expansion I/O Unit, or
Expansion Unit connected immediately before the Temperature Sensor Unit.
Negative values are stored as 2’s complements.
Data for range codes that include one digit after the decimal point are
stored without the decimal point, i.e., 10 times the actual value is stored.
If the input temperature exceeds the maximum or minimum value in the
temperature input range that has been set by ±20
°C or ±20°F, the dis-
played value will be held.
If the circuit is disconnected, the open-circuit detection function will oper-
rate and the converted temperature data will be set to 7FFF.
The open-circuit detection function will be automatically cleared and nor-
mal input temperature conversion will begin automatically when the input
temperature returns to the convertible range.
Input Data conversion examples
Unit: 0.1°CK or J ×10 500.0°C 5000 1388 hex
20.0°C 200 FF38 hex
200.0°C 2000 F830 hex
None
CP1W-TS003
Temperature Sensor Unit
CP1H
Input word
addresses
Output word
addresses
CIO 0
CIO 1
CIO 100
CIO 101
CIO 2
CIO 3
CIO 4
CIO 5
m+1
Converted temperature data from input 0
m+2
Converted temperature data from input 1
m+3
Converted temperature data from input 2
m+4
Converted temperature data from input 3