209
Error Log Section 8-3
0300 Parameter error; packet discarded Commands
Bit 15: OFF
Bits 08 to 14: SNA
Bits 00 to 07: SA1
Responses
Bit 15: ON
Bits 08 to 14: DNA
Bits 00 to 07: DA1
Check the command format and
set the correct command data.
---
03C0 FINS/TCP setting error 01 to 10:
Connection
number
01: Automati-
cally allo-
cated FINS
node address
duplication
02: Destina-
tion IP
address error
03: Destina-
tion port
number error
Refer to 1-5-1 FINS Communica-
tions Service in this manual and
the Operation Manual, Construc-
tion of Applications: SECTION 7
and set the FINS/TCP settings
correctly.
---
03C1 Server setting error 00: DNS
01: SMTP
02: POP3
03: SNTP
01: IP
address
02: Host
name
03: Port num-
ber
04: Other
parameters
Set the server settings correctly
based on the information in the
detailed error code.
---
Error
code
Meaning Detailed error code Correction EE-
PROM
1st byte 2nd byte