Page #237 background image
211
Error Log Section 8-3
03C4 Server connection error 00: DNS
01: SMTP
02: POP3
03: SNTP
01: Specified
host does not
exist
02: No ser-
vice at speci-
fied host
03: Timeout
04: Closed
unilaterally by
host
05: Cannot
connect
because
account infor-
mation does
not match
06: Host
name resolu-
tion error
07: Transmis-
sion error
08: Recep-
tion error
09: Other
error
Take either of the following mea-
sures.
• Correct the settings for each
server.
• Inspect the communications path
(Ethernet Unit, cable connec-
tions, hub, router, server), and
correct the situation that is caus-
ing the error.
---
03C5 Mail communications error F101: Mail too large
F102: Mail received from
non-specified address
F103: Mail subject error
F104: Non-specified com-
mand received
F106: Mail format (header)
error
F107: Mail format (body)
error
F201: Parameter error
F301: Decoding error
F302: File attachment error
(filename error, data format
error, I/O memory write size
error)
F303: No attached file
F304: Non-specified file
attachment received
F305: File attachment too
large
Other: FINS error response
code
Refer to the Operation Manual,
Construction of Applications: Cre-
ating FINS Applications, and cor-
rect the remote node (i.e., the
application on the personal com-
puter).
---
03C6 Clock data write error 0001: Clock data could not
be refreshed because of a
CPU Unit error.
Clear the CPU Unit error. ---
0002: Clock data could not
be refreshed because the
CPU Unit could not write
clock data in that operation
mode.
Refer to the Operation Manual,
Construction of Applications:
Automatic Clock Adjustment
Function, and check the operat-
ing conditions.
---
Error
code
Meaning Detailed error code Correction EE-
PROM
1st byte 2nd byte

Table of Contents

Other manuals for Omron CS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CS Series and is the answer not in the manual?

Omron CS Series Specifications

General IconGeneral
BrandOmron
ModelCS Series
CategoryNetwork Hardware
LanguageEnglish

Related product manuals