6 - 19
6 Parameters
E5@C-T Digital Temperature Controllers User’s Manual (H185)
6-4 Program Setting Level
6
pr
Segment n Slope (n = 0 to 31)
The Displayed Segment Selection parameter must
not be set to END. The Step Time/Rate of Rise
Programming parameter must be set to Rate of
Rise. The Segment Type parameter must be set to
Ramp.
This parameter sets the amount of change per the time unit of the slope for the specified
segment number.
If this parameter is set to 0, the segment will be a step segment.
z Related Sections
5-15 Program-related Functions (page 5-53)
z Related Parameters
Step Time/Rate of Rise Programming (Initial Setting Level): Page 6-59
Segment n Format (Program Setting Level): Page 6-18
time
Segment n Time (n = 0 to 31)
The Display Segment Selection parameter must not
be set to END. The Step Time/Rate of Rise
Programming must be set to Step Time, or the Step
Time/Rate of Rise Programming must be set to
Rate of Rise and the Segment Type parameter must
be set to Soak.
This parameter sets the segment time for the specified segment number.
This parameter sets the soak segment time for rate of rise programming.
* The unit is set in the Program Time Unit parameter. (The default is H-M (hours and min-
utes).)
z Related Sections
5-15 Program-related Functions (page 5-53)
z Related Parameters
Step Time/Rate of Rise Programming (Initial Setting Level): Page 6-59
Segment n Format (Program Setting Level): Page 6-18
Function
Setting
Setting range Unit Default
0 to 9999 EU 0
See
See
Function
Setting
Setting range Unit Default
0.00 to 99.59 Hours and minutes, or minutes and seconds 0.00
See
See