6 Parameters
6 - 70
E5@C-T Digital Temperature Controllers User’s Manual (H185)
alh1
Alarm 1 Hysteresis
Alarm 1 must be assigned.
The alarm 1 type must not be 0, 12, or 13.
alh2
Alarm 2 Hysteresis
Alarm 2 must be assigned.
The alarm 2 type must not be 0, 12, or 13.
alh3
Alarm 3 Hysteresis
Alarm 3 must be assigned.
The alarm 3 type must not be 0, 12, or 13.
alh4
Alarm 4 Hysteresis
Alarm 4 must be assigned.
The alarm 4 type must not be 0, 12, or 13.
• These parameters set the hysteresis for alarms 1, 2, 3, and 4.
Alarms Other Than an MV Alarm
MV Alarms
z Related Parameters
Alarm Value 1 to 4 (Operation Level): Page 6-20
Alarm Value Upper Limit 1 to 4 and Alarm Value Lower Limit 1 to 4 (Operation Level):
Page 6-21
Alarm 1 to 4 Type (Initial Setting Level): Page 6-66
Standby Sequence Reset (Advanced Function Setting Level): Page 6-83
Auxiliary Output 1 to 4 Open in Alarm (Advanced Function Setting Level): Page 6-84
Alarm 1 to 4 Latch (Advanced Function Setting Level): Page 6-89
Function
Setting
Setting range Unit Default
Temperature input 0.1 to 999.9 °C or °F 0.2
Analog input 0.01 to 99.99 %FS 0.02
Setting range Unit Unit
0.01 to 99.99 % 0.50
See
See