6 - 89
6 Parameters
E5@C-T Digital Temperature Controllers User’s Manual (H185)
6-10 Advanced Function Setting Level
6
a1lt
Alarm 1 Latch
Alarm 1 must be assigned, and the alarm 1 type
must not be 0.
a2lt
Alarm 2 Latch
Alarm 2 must be assigned, and the alarm 2 type
must not be 0 or 12.
a3lt
Alarm 3 Latch
Alarm 3 must be assigned, and the alarm 3 type
must not be 0 or 12.
a4lt
Alarm 4 Latch
Alarm 4 must be assigned, and the alarm 4 type
must not be 0 or 12.
When this parameter is set to ON, the alarm function is held until one of the following
conditions is satisfied.
a The power is cycled.
b The latch is cancelled by the PF Key.
(PF Setting = LAT: Alarm Latch Cancel)
c The latch is cancelled by an event input.
(Event Input Assignment 1 to 6 = LAT: Alarm Latch Cancel)
The output is turned OFF when switching to the Initial Setting Level, Communications
Setting Level, Advanced Function Setting Level, or Calibration Level.
If an auxiliary output is set to close in alarm, the output is kept closed. If it is set to open in
alarm, it is kept open.
z Related Parameters
Alarm Value 1 to 4 (Operation Level): Page 6-20
Alarm Value Upper Limit 1 to 4 and Alarm Value Lower Limit 1 to 4 (Operation Level):
Page 6-21
Alarm 1 to 4 Type (Initial Setting Level): Page 6-66
Standby Sequence Reset (Advanced Function Setting Level): Page 6-83
Event Input Assignment 1 to 6 (Initial Setting Level): Page 6-74
Auxiliary Output 1 to 4 Open in Alarm (Initial Setting Level): Page 6-84
Alarm 1 to 4 Hysteresis (Initial Setting Level): Page 6-70
HB ON/OFF (Advanced Function Setting Level): Page 6-84
PF Setting (Advanced Function Setting Level): Page 6-105
Function
Setting
Setting range Default
on: Enabled, off: Disabled off
See
See