6 Parameters
6 - 90
E5@C-T Digital Temperature Controllers User’s Manual (H185)
prlt
Move to Protect Level Time
This parameter sets the key pressing time required to move to the Protect Level from the
Operation Level, Program Setting Level, Adjustment Level, PID Setting Level, or
Monitor/Setting Item Level.
cjc
Cold Junction Compensation
Method
Input type must be thermocouple or infrared
temperature sensor
This parameter specifies whether cold junction compensation is to be performed
internally by the Controller or to be performed externally when the input type setting is 5
to 24.
The cold junction compensation external setting is enabled when the temperature
difference is measured using two thermocouples or two ES1B Sensors.
z Related Parameters
Input Type (Initial Setting Level): Page 6-56
Function
Setting
Setting range Unit Default
1 to 30 Seconds 3
Function
Setting
Setting range Default
on: Internally, off: Externally on