6 Parameters
6 - 94
E5@C-T Digital Temperature Controllers User’s Manual (H185)
hsu
HS Alarm Use HB and HS alarms must be supported.
• Set this parameter to use HS alarms.
hsl
HS Alarm Latch
HB and HS alarms must be supported.
The HS Alarm Use parameter must be set to ON.
• When this parameter is set to ON, the HS alarm is held until any of the following
conditions is satisfied.
a The HS alarm current is set to 50.0 A.
b The power is cycled.
c The latch is cancelled by the PF Key.
(PF Setting = LAT: Alarm Latch Cancel)
d The latch is cancelled by an event input.
(Event Input Assignment 1 to 6 = LAT: Alarm Latch Cancel)
• Output is turned OFF when switching to the Initial Setting Level, Communications Setting
Level, Advanced Function Setting Level, or Calibration Level.
z Related Parameters
HS Alarm Use (Advanced Function Setting Level): Page 6-94
Event Input Assignment 1 to 6 (Initial Setting Level): Page 6-74
HB ON/OFF (Advanced Function Setting Level): Page 6-84
PF Setting (Advanced Function Setting Level): Page 6-105
Function
Setting
Setting range Default
on: Enabled, off: Disabled on
Function
Setting
Setting range Default
on: Enabled, off: Disabled off