2 Preparations
2 - 4
E5@C-T Digital Temperature Controllers User’s Manual (H185)
z E5AC-T
Waterproofing is not possible when group mounting several Controllers.
The recommended panel thickness is 1 to 5 mm for the E5CC-T, and 1 to 8 mm for E5EC-T, and
E5AC-T.
Controllers must not be closely mounted vertically. (Observe the recommended mounting space
limits.)
When two or more Digital Controllers are mounted, make sure that the surrounding temperature does
not exceed the allowable operating temperature specified in the specifications.
* For E5EC-T models with two control outputs (QQ, QR, CQ, RR, CC, or PR) and 019, 020, 021, or 022
options (shown below), the ambient temperature for group mounting must be 45°C max.
To mount these models at an ambient temperature of 55°C, install them at the following intervals.
Individual Mounting
120 min.
+1.0
0
Group Mounting
(96 × number of Units 3.5)
92
+0.8
0
92
+0.8
0
92
+0.8
0
E5EC-T-@@ @ @ @ M-@@@
QQ, QR,
RR, CC, CQ, PR
019, 020,
021, 022
45
+0.6
0
92
120 min.
+0.8
0
60 min.