6 Parameters
6 - 110
E5@C-T Digital Temperature Controllers User’s Manual (H185)
This parameter sets the password to move to the Calibration Level.
burn
Burnout Method
This parameter specifies whether the input value when an input error occurs is to be
treated as the upper limit or the lower limit.
The setting of this parameter applies to alarms, a PV transfer output, or automatic PID set
selection with the PV/DV.
pmst
Parameter Mask Setting
You can use a key operation to hide parameters that do not need to be displayed.
This allows you to prevent incorrect operations for parameters or to change the parameter
display configuration according to the application.
If you set the Parameter Mask Setting parameter to ON, Parameter Mask Mode is entered.
Refer to 5-7-1 Parameter Mask Settings (page 5-21) for information on masking parameters
after you enter Parameter Mask Mode.
z Related Parameter
Parameter Mask Enable (Protect Setting Level): Page 6-5
cmoV
Move to Calibration Level Initial setting/communications protect must be 0.
Set the password to move to the Calibration Level. The password is 1201.
Move to the Calibration Level either by pressing the M Key or O Key or by waiting for two
seconds to elapse.
z Related Parameter
Initial Setting/Communications Protect (Protect Level): Page 6-4
Function
Setting
Setting range Default
up: Up-scale, down: Down-scale up
Function
Operation
See
See
Function
See
See