List of Input Types
Input type Specifications Set value Temperature range in °C Temperature range in °F
Resistance
thermometer
Pt100 0 200 to 850 300 to 1500
1 199.9 to 500.0 199.9 to 900.0
2 0.0 to 100.0 0.0 to 210.0
JPt100 3 199.9 to 500.0 199.9 to 900.0
4 0.0 to 100.0 0.0 to 210.0
Thermocouple K
5* 200 to 1300 300 to 2300
6 20.0 to 500.0 0.0 to 900.0
J7100 to 850 100 to 1500
8 20.0 to 400.0 0.0 to 750.0
T9200 to 400 300 to 700
10 199.9 to 400.0 199.9 to 700.0
E11200 to 600 300 to 1100
L12100 to 850 100 to 1500
U13200 to 400 300 to 700
14 199.9 to 400.0 199.9 to 700.0
N15200 to 1300 300 to 2300
R 16 0 to 1700 0 to 3000
S 17 0 to 1700 0 to 3000
B 18 100 to 1800 300 to 3200
W 19 0 to 2300 0 to 3200
PLII 20 0 to 1300 0 to 2300
Infrared temperature
sensor ES1B
10 to 70°C 21 0 to 90 0 to 190
60 to 120°C 22 0 to 120 0 to 240
115 to 165°C 23 0 to 165 0 to 320
140 to 260°C 24 0 to 260 0 to 500
Current input 4 to 20 mA 25 One of the following ranges according to the scaling:
1999 to 9999
199.9 to 999.9
19.99 to 99.99
1.999 to 9.999
0 to 20 mA 26
Voltage input 1 to 5 V 27
0 to 5 V 28
0 to 10 V 29

Table of Contents