EasyManua.ls Logo

Omron E5AN-H

Omron E5AN-H
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
87
Shifting Input Values Section 4-1
4-1 Shifting Input Values
4-1-1 Shifting Inputs
Either a 1-point shift or a 2-point shift can be used to shift the input. The
default setting is for a 1-point shift. To execute a 2-point shift, change the Input
Shift Type parameter setting (advanced function setting level) to INS2.
There is no shift function for analog inputs. Use scaling for fine adjustments.
One-point shift
With a 1-point shift, the value set for the Temperature Input Shift parame-
ter (adjustment level) is applied to each point in the entire temperature
input range. For example, if the input shift value is set to 1.2°C, the pro-
cess value is treated as 201.2°C after the input shift is applied when the
measured process value is 200°C.
Operating Procedure In this example, the input from a K sensor is shifted by 1°C using a 1-point
input shift.
ins
Temperature
Input Shift
0
100
Temperature
Upper limit
Lower limit
Before
shifting
After shifting
Input shift value
Input
Operation Level
Operation Level
Adjustment Level
1. Press the O Key to move from the operation level to the adjustment level.
2. Select the Temperature Input Shift parameter by pressing the M Key.
3. Press the U or D Key to set 1.00.
Operation Level
4. To return to the operation level, press the O Key. The process value is
1°C larger than before the shift was applied.
C
30.0
200.0
l.adj
Adjustment
Level Display
C
ins
0.00
Temperature
Input Shift
C
ins
1.00
C
31.0
200.0

Table of Contents

Other manuals for Omron E5AN-H

Related product manuals