EasyManua.ls Logo

Omron E5AN-H

Omron E5AN-H
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
60
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
3-8 Determining PID Constants (AT, ST, Manual Setup)
3-8-1 AT (Auto-tuning)
When AT is executed, the optimum PID constants for the set point at that
time are set automatically. A method (called the limit cycle method) for
forcibly changing the manipulated variable and finding the characteristics
of the control object is employed.
Either 40% AT or 100% AT can be selected depending on the width of MV
variation in the limit cycle. In the AT Execute/Cancel parameter, specify
at-2 (100% AT) or at-1 (40% AT). To cancel AT, specify off (AT can-
cel).
Only 100% AT can be executed for heating and cooling control or for float-
ing control for position-proportional models.
AT cannot be executed when control has stopped or during ON/OFF con-
trol.
The results of AT are reflected in the Proportional Band (P), Integral Time
(I), and Derivative Time (D) parameters for the PID set at the time AT exe-
cution starts. For details on PID sets, refer to PID Sets on page 129.
AT Operations AT is started when either at-2 (100% AT) or at-1 (40% AT) is specified for
the AT Execute/Cancel parameter. During execution, the AT Execute/Cancel
parameter on the No. 1 display flashes. When AT ends, the AT Execute/Can-
cel parameter turns OFF, and the No. 1 display stops flashing.
If you move to the operation level during AT execution, the No. 2 display
flashes to indicate that AT is being executed.
Only the Communications Writing, RUN/STOP, AT Execution/Cancel, and Pro-
gram Start parameters can be changed during AT execution. Other parame-
ters cannot be changed.
at
.i
233.0
C
.p
(0
.d
40.0
PID Setting Level
PID* Proportional Band
PID* Integral Time
PID* Derivative Time
(
: 1 to 8)
at
off
at
at-2
AT Execute/Cancel
No. 1 displa
100% AT execution in progress
C
25.0
100.0
C
25.0
100.0
PV/SP
AT execution in progress
No. 2 display

Table of Contents

Other manuals for Omron E5AN-H

Related product manuals