EasyManua.ls Logo

Omron E5AN-H

Omron E5AN-H
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
125
Using the Transfer Output Section 4-14
The operation differs for models with a transfer output and models without
a transfer output for which control output 1 or control output 2 is used as a
simple transfer output, as shown in the following table.
Transfer Output
Destination
Precision and User Calibration
Note For details on the calibration method, refer to SECTION 6 CALI-
BRATION.
Transfer Output Type
Note (1) The default is OFF. For a Controller that does not support a transfer out-
put, the item specified for the Control Output 1 Assignment or Control
Output 2 Assignment parameter will be output.
(2) The output value will be different between when the Transfer Output Type
parameter is set to a heating control output or cooling control output, and
when the Control Output 1 Assignment or Control Output 2 Assignment
parameter is set to a heating control output or cooling control output.
Example: When a Current Output Is Set to 4 to 20 mA and MV Monitor
(Heating) Is Selected
When used as a transfer output, 4.0 mA will be output for 0% and
20.0 mA will be output for 100%.
Transfer
output
Control output 1 Control output 2 Transfer output
destination
Yes --- --- Transfer output
No Current output or linear
voltage output
None, relay output, voltage
output (for driving SSR), or
SSR output
Control output 1
No Current output or linear
voltage output
Current output or linear
voltage output
Control output 1
No Relay output, voltage
output (for driving
SSR), or SSR output
Current output or linear
voltage output
Control output 2
No Relay output, voltage
output (for driving
SSR), or SSR output
None, relay output, voltage
output (for driving SSR), or
SSR output
None
Precision User calibration
Transfer output ±0.3% FS Supported. (See note.)
Simple transfer out-
put
Not specified. Not supported.
Transfer output type Symbol Setting range
OFF (See note 1.) off ---
Set point sp SP lower limit to SP upper limit
Set point during SP ramp sp-m SP lower limit to SP upper limit
PV pv Input setting range lower limit to input set-
ting range upper limit or
Scaling lower limit to scaling upper limit
MV monitor (heating)
(See note 4.)
mv 5.0 to 105.0 (heating/cooling control: 0.0 to
105.0) (See note 2.)
MV monitor (cooling)
(See note 5.)
c-mv 0.0 to 105.0 (See note 2.)
Valve opening (See note
6.)
v-m 10.0 to 110.0

Table of Contents

Other manuals for Omron E5AN-H

Related product manuals