Initial Setting Examples Section 3-1
Example 3
stop
run
M
M
25.0
0.0
M
M
M
mot
45
in-t
5
clfl
flot
5
45
flot
clos
250.0
25.0
250.0
c
25.0
250.0
c
r-5
run
c
at
off
M
sprt
10.0
10.0
250.0
Input type: 5 (K thermocouple,
200.0°C to 1,300.0°C)
Control method: Floating control (default)
SP ramp time unit: EU/min (default)
Travel time: 45 s
SP ramp set value: 10.0 EU (°C)
Set point: 250°C
Setup Procedure
Power ON
Initial Setting
Level
Set input
specifications
Set control
specifications
Adjustment
Level
Start operation
Power ON
Operation Level
PV/SP
Press the O key for
at least 3 s.
Control stops.
Initial Setting
Level
Press the O key for
at least 1 s.
Operation Level
Use the U and
D keys to set the
SP to 250.0°C.
PV/SP:
Adjustment
Level
Press the O key
(for less than 1 s).
Control starts.
Operation Level
Confirm that
control is running.
Running
Stopped
Start o
p
eration.
PV/SP:
Press the O key
(for less than 1 s).
Set travel time
Set SP ramp
Check input type.
Input Type:
Check that control
method is floating
control.
Floating
control:
Close control:
Use the
U and D
keys to set the
travel time to 45.
Travel time:
Use the
U and D
keys to set the SP
ramp set value to
10.0°C.
SP ramp set value: