xxv
■ Ratings
■ Characteristics
Previous models Upgraded models
Input sensor types for ther-
mocouple inputs
--- The following types of thermocouple input
were added: W and PLII.
Input range for E thermocouple: 0 to 600°C Input range increased for E thermocouple:
−200 to 600°C
Input accuracy
(There are no changes in
thermocouple specifications
for E5CN-U.)
• Thermocouple: (±0.5% PV or ±1°C, which-
ever is greater) ±1 digit
• Platinum resistance thermometer:
(±0.5%PV or ±1°C, whichever is greater)
±1 digit
• Analog input: ±0.5% FS ±1 digit
• Thermocouple: (±0.3% PV or ±1°C, which-
ever is greater) ±1 digit
• Platinum resistance thermometer: (±0.2%
PV or ±0.8°C, whichever is greater)
±1 digit
• Analog input: ±0.2% FS ±1 digit
Influence of signal source
resistance
• Thermocouple: 0.1°C/Ω (except B, R, S),
0.2°C/Ω (B, R, S)
• Platinum resistance thermometer: 0.4°C/Ω
• Thermocouple: 0.1°C/Ω (for all specifica-
tions)
• Platinum resistance thermometer: 0.1°C/Ω
Current outputs Current output resolution: Approx. 2,700 Current output resolution: Approx. 10,000
Auxiliary outputs
(alarm outputs)
E5CN/E5CN-U/E5GN
250 VAC, 1 A
E5CN/E5CN-U E5GN
250 VAC, 3 A 250 VAC, 2 A
Input sampling cycle E5GN
500 ms
E5GN
250 ms
Previous models Upgraded models
Model numbers for the E5CN Models with 24-VAC/VDC power supply
specifications
Example: E5CN-R2MT-500 (24 VAC/VDC)
A “D” was added to the model numbers for
models with 24-VAC/VDC power supply
specifications.
Example: E5CN-R2MTD-500 (24 VAC/VDC)
Model numbers for the
E5AN/EN
Example: E5AN-R3MT-500 (100 to 240
VAC)
Example: E5AN-R3MT-500 (24 VAC/VDC)
“-N” was added to all model numbers
A “D” was added to the model numbers for
models with 24-VAC/VDC power supply
specifications.
Example:
• E5AN-R3MT-500-N (100 to 240 VAC)
• E5AN-R3MTD-500-N (24 VAC/VDC)
Model numbers for the
E5GN
Examples: E5GN-RTC (100 to 240 VAC)
E5GN-RP (100 to 240 VAC)
24-VAC/DC Specification
Example: E5GN-RTC (24 VAC/DC)
• Model numbers have changed accompa-
nying the introduction of universal input
capability.
• A “D” was added to the model numbers for
models with 24-VAC/VDC power supply
specifications.
Example: E5GN-RT (100 to 240 VAC)
E5GN-RTD (24 VAC/VDC)
Front panel --- PV status display and SV status display
PF Key added (E5AN/EN only).
--- PV/SP display selection for three-level dis-
play (E5AN/EN only) *