3 Communications Data for CompoWay/F
3 - 16
E5@C Digital Temperature Controllers Communications Manual (H175)
C3 (83) 0059 PV Dead Band H'00000000 to H'0000270F (0 to 9999)
Advanced
function setting
C3 (83) 005B Manual MV Limit
Enable
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83) 005C Direct Setting of
Position Proportional
MV
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83) 005D AT Calculated Gain H'00000001 to H'00000064 (0.1 to 10.0)
C3 (83) 005E AT Hysteresis H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 9.99 for analog input)
C3 (83) 005F Limit Cycle MV
Amplitude
H'00000032 to H'000001F4 (5.0 to 50.0)
C3 (83) 0060 Remote SP Enable H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83) 0061 Remote SP Upper
limit
Input range lower limit to Input range upper
limit for temperature input
Scaling lower limit to Scaling upper limit for
analog input
C3 (83) 0062 Remote SP Lower
limit
Input range lower limit to Input range upper
limit for temperature input
Scaling lower limit to Scaling upper limit for
analog input
Advanced
function setting
C3 (83) 0063 SP Tracking H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83) 0067 PV Rate of Change
Calculation Period
H'00000001 to H'000003E7 (1 to 999)
C3 (83) 0068 Heating/Cooling
Tuning Method
H'00000000 (0): Same (Same as for heating.)
H'00000001 (1): Linear
H'00000002 (2): Air cooling
H'00000003 (3): Water cooling
C3 (83) 006C Extraction of Square
Root Enable
H'00000000 (0): OFF
H'00000001 (1): ON
Initial setting
Variable
type
Address Parameter name Setting (monitor) value Level