2-2 Part Names and Functions
2-9
NS7 Front Panel
RUN Indicator Status
Indicator Green Orange Red
Lit PT is operating normally. The file system check that is
performed immediately after the
power is turned ON is in prog-
ress.
The battery power is low, or the
battery is not connected and the
PT is operating normally.
Not used.
Flashing Memory Card transfer ended
normally.
A backlight error occurred
immediately after power was
turned ON.
Memory Card transfer in progress. Memory Card
transfer ended
abnormally.
Not lit Power is not being supplied to the PT.
The fuse is broken.
The system program is damaged and the system cannot be booted.
Display
7.7-inch color STN LCD
The entire display is a touch
panel that serves as an input
device.
RUN indicator
Lights or flashes to indicate the
status of the PT.

Table of Contents