19
● Control output
A common terminal for the four control outputs of the SS2 series is the output ground common (13 pin).
For the G5 series, be careful to install wiring because a common terminal is for each control output.
*1. Functions are changed by using Control Mode Selection (Pn02). It operates as the Positioning Completed Output
(INP), at the default setting 2: Advanced Position Control or 0: High-response Position Control. When you set 1:
Internally Set Speed Control, it operates as the Servomotor Rotation Speed Detection Output (TGON).
*2. Set a function to output by using Warning Output Selection (Pn09). The default setting is 2: Output for regeneration,
overload, or fan rotation speed alarm warning.
*3. Set a function to output by using Output Signal Selection 4 (Pn413). The default setting is Positioning completion
output 1/Motor rotation speed detection output.
*4. Set a function to output by using Output Signal Selection 1 (Pn410). The default setting is Brake interlock output.
*5. Set a function to output by using Output Signal Selection 2 (Pn411). The default setting is Servo ready completed.
[Electrical specifications]
● In both the SS2 and the G5 series
• Control output: Maximum service voltage: 30 VDC, Maximum output current: 50 mA
● Encoder output
Wire encoder outputs, e.g. when you convey the encoder information to the host controller.
*1. The common terminals (GND/ZGND) of Phase-Z Output (Z) and Encoder phase-Z output (Z) are the grounds common
to all encoder outputs.
[Electrical specifications]
● In both the SS2 and the G5 series
• Encoder phase-A/B/Z output: Line driver AM26C31 or equivalent
• Open collector output: Maximum service voltage: 30 VDC, Maximum output current: 50 mA