3-21
3-7 Parameter List
3
Operation
Extended Function Mode
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
Basic setting
A001
Frequency reference
selection
00: Digital Operator (FREQ adjuster)
(Enabled when 3G3AX-OP01 is used.)
01: Terminal
02: Digital Operator (F001)
03: ModBus communication
04: Option 1
05: Option 2
06: Pulse train frequency
07: Not used
10: Operation function result
02 No
4-10
4-138
A002
RUN command
selection
01: Terminal
02: Digital Operator (F001)
03: ModBus communication
04: Option 1
05: Option 2
02 No 4-11
A003 Base frequency 30. to Maximum frequency [A004] 50.
No Hz
4-11
4-110
A203 * 2nd base frequency 30. to 2nd maximum frequency [A204] 50.
4-11
A303 * 3rd base frequency 30. to 3rd maximum frequency [A304] 50.
A004 Maximum frequency 30. to 400. 50.
No Hz 4-12
A204
* 2nd maximum
frequency
30. to 400. 50.
A304
* 3rd maximum
frequency
30. to 400. 50.
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001