3-33
3-7 Parameter List
3
Operation
Others
b046
Reverse rotation
prevention selection
00: Disabled
01: Enabled
00 No 4-59
b050
Selection of non-stop
function at
momentary power
interruption
00: Disabled
01: Enabled (deceleration stop)
02: Enabled (without recovery)
03: Enabled (with recovery)
00 No
4-60
b051
Starting voltage of
non-stop function at
momentary power
interruption
0.0 to 999.9
1000.
220/
440
No V
b052
Stop deceleration
level of non-stop
function at
momentary power
interruption
0.0 to 999.9
1000.
360/
720
No V
b053
Deceleration time of
non-stop function at
momentary power
interruption
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
1.00 No s
b054
Deceleration starting
width of non-stop
function at
momentary power
interruption
0.00 to 10.00 0.00 No Hz
b055
Proportional gain
setting of non-stop
function at
momentary power
interruption
0.00 to 2.55 0.20 Yes
b056
Integral time setting
of non-stop function
at momentary power
interruption
0.000 to 9.999/10.00 to 65.53
0.100
Yes s 4-60
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.