EasyManua.ls Logo

Omron RX - Page 82

Omron RX
414 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-33
3-7 Parameter List
3
Operation
Others
b046
Reverse rotation
prevention selection
00: Disabled
01: Enabled
00 No 4-59
b050
Selection of non-stop
function at
momentary power
interruption
00: Disabled
01: Enabled (deceleration stop)
02: Enabled (without recovery)
03: Enabled (with recovery)
00 No
4-60
b051
Starting voltage of
non-stop function at
momentary power
interruption
0.0 to 999.9
1000.
220/
440
No V
b052
Stop deceleration
level of non-stop
function at
momentary power
interruption
0.0 to 999.9
1000.
360/
720
No V
b053
Deceleration time of
non-stop function at
momentary power
interruption
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
1.00 No s
b054
Deceleration starting
width of non-stop
function at
momentary power
interruption
0.00 to 10.00 0.00 No Hz
b055
Proportional gain
setting of non-stop
function at
momentary power
interruption
0.00 to 2.55 0.20 Yes
b056
Integral time setting
of non-stop function
at momentary power
interruption
0.000 to 9.999/10.00 to 65.53
0.100
Yes s 4-60
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.

Table of Contents

Related product manuals