3-7 Parameter List
3
Operation
Others
b034
RUN time/Power ON
time setting
0. to 9999. (0 to 99990)
1000 to 6553 (10000 to 655300)
0. No h 4-52
b035
Rotation direction
limit selection
00: Forward and Reverse are enabled
01: Only Forward is enabled.
02: Only Reverse is enabled.
00 No 4-52
b036
Reduced voltage
startup selection
0 (Reduced voltage startup time: small) to
255 (Reduced voltage startup time: large)
6No 4-53
Others
b037 Display selection
00: Complete display
01: Individual display of functions
02: User setting
03: Data comparison display
04: Basic display
04 No 4-53
b038
Initial screen
selection
00: Screen when the Enter key was pressed
last
01: d001
02: d002
03: d003
04: d007
05: F001
01 No 4-56
b039
User parameter
automatic setting
function selection
00: Disabled
01: Enabled
00 No 4-57
Torque limit
b040 Torque limit selection
00: Four-quadrant separate setting
01: Terminal switch
02: Analog input
03: Option 1
04: Option 2
00 No -
4-57
4-59
b041
Torque limit 1
(Four-quadrant mode
forward power
running)
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
no (Torque limit disabled)
150. No %
4-57
4-59
b042
Torque limit 2
(Four-quadrant mode
reverse regeneration)
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
no (Torque limit disabled)
150. No %
4-57
4-59
b043
Torque limit 3
(Four-quadrant mode
reverse power
running)
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
no (Torque limit disabled)
150. No %
b044
Torque limit 4
(Four-quadrant mode
forward regeneration)
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
no (Torque limit disabled)
150. No %
b045
Torque LADSTOP
selection
00: Disabled
01: Enabled
00 No 4-59
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001