Wiring Section 3-3
Maximum Recommended Current:
The values listed in the table above are for bundles of up to 4 wires. If 5 or
more wires are bundled together, reduce the max. current to 80% of the listed
current.
The following chart shows only the relationship between the voltage drop per
meter and the current and wire length. Be sure that the current actually being
used does not exceed the max. recommended current.
Voltage Drop per Meter
(UL1015 Heat-resistant
PVC Wire)
Wiring the Power
Supply and Branch
Outputs
Use a DC power supply with sufficient capacity and little voltage fluctuation,
i.e., 24 VDC +10/
−20%.
Voltage drop (mV)
The current
shown is the al-
lowed current.
In actual appli-
cations, use a
current below
the maximum
recommended
current.
Current (A)