61
Shared Parameter Settings Section 4-7
Setting the Overvoltage Alarm Value: V-O (Voltage Over)
If the Down Key ( ) is pressed from the undervoltage alarm value setting dis-
play (V-U), the display will switch to the overvoltage alarm value setting dis-
play (V-O).
Note If the voltage exceeds the SV for 80 ms, the Alarm Output (ALM) will be
turned OFF and the seven-segment display will alternate between error code
A20 and the measured voltage.
The alarm output can be cleared after the voltage falls below the SV
−0.3 V for
more than 500 ms.
V -
o
2 (
(
2 &
4
(Return to V-O display.)
23
4
°C
kh
V
A
s
1
23
4
°C
kh
V
A
s
1
23
4
°C
kh
V
A
s
1
This parameter sets the overvoltage alarm value.
Press the Key to display the overvoltage
alarm's set value (SV). The SV can be changed by
pressing the and Keys (see note).
The setting range is 20.0 to 28.8 V (0.1 V units).
Note If the or Key is pressed for more than 2 s,
the SV will change in 1.0 V units instead of 0.1 V
units.
Change the SV with the and Keys.
The S8M will automatically return to the V-O dis-
play if no key is pressed within 3 s.
Switch to the
run time value
setting.
When the Key is pressed, the SV display will
flash. When the flashing stops, the new setting will
be saved and the S8M will return to V-O display.
If you want to confirm the new setting, press the
Key again from the V-O display.