Shared Parameter Settings Section 4-7
Setting the Run Time Value: TIM (Time)
If the Down Key ( ) is pressed from the overvoltage alarm value setting dis-
play (V-O), the display will switch to the run time value setting display (TIM).
Note When the run time exceeds the SV, the Alarm Output (ALM) will be turned
OFF and the seven-segment display will alternate between error code A23
and the measured run time.
Set the run time value to 0.0 kh when run time alarms are not required.
The run time (PV) can be cleared to reset the timer. For details, refer to
page 71.
When an alarm is being output because the run time exceeds the alarm value
(SV), the alarm output can be cleared by clearing the run time (PV).
t i
m
* 0
% 0
(Return to TIM display.)
23
4
°C
kh
V
A
s
1
23
4
°C
kh
V
A
s
1
23
4
°C
kh
V
A
s
1
This parameter sets the run time value.
Press the Key to display the run time alarm's set
value (SV). The SV can be changed by pressing the
and Keys (see note).
The setting range is 0.0 to 99.9 kh (99,900 h), set in
100 hour units.
Note If the or Key is pressed for more than 2 s, the
SV will change in 1.0 kh units instead of 0.1 kh units.
The run time alarm won't be output if the SV is set to
0.0 kh.
Change the SV with the and Keys.
The S8M will automatically return to the TIM display
if no key is pressed within 3 s.
Switch to the
over-tempera-
ture output
value setting.
When the Key is pressed, the SV display will
flash. When the flashing stops, the new setting
will be saved and the S8M will return to TIM dis-
play.
If you want to confirm the new setting, press the
Key again from the TIM display.