63
Shared Parameter Settings Section 4-7
Setting the Over-temperature Output Value: TMP (Temperature)
If the Down Key ( ) is pressed from the run time value setting display (TIM),
the display will switch to the over-temperature output value setting display
(TMP).
Note (1) If the temperature exceeds the SV for more than 1 s, the over-tempera-
ture output (TMP) will be turned OFF and the seven-segment display will
alternate between error code A30 and the measured temperature.
(2) The error display and over-temperature output are reset automatically af-
ter the temperature falls and remains below the set value
− 3°C for more
than 5 s.
(3) The over-temperature output (TMP) operates independently of the other
external outputs. This output can be received as a normally closed output
and used to start an exhaust fan or air conditioner to reduce the temper-
ature in the control panel. (For details, refer to page 28.)
t
p
m
8
0
7 0
(Return to TMP displa
.)
23
4
°C
kh
V
A
s
1
23
4
°C
kh
V
A
s
1
23
4
°C
kh
V
A
s
1
This parameter sets the over-temperature output value.
Press the Key to display the over-temperature
output value (SV). The SV can be changed by
pressing the and Keys (see note).
The setting range is 25°C to 80°C. Change the SV
with the and Keys (see note).
The S8M will automatically return to the TMP dis-
play if no key is pressed within 3 s.
Note If the or Key is pressed for more than 2 s,
the SV will change in 10°C units instead of 1°C
units.
Switch to the
startup
sequence set-
ting.
When the Key is pressed, the SV display will
flash. When the flashing stops, the new setting will
be saved and the S8M will return to TMP display.
If you want to confirm the new setting, press the
Key again from the TMP display.