Why is the Omron Surge Protector circuit cut off as soon as power is supplied?
- PPatricia ProctorAug 25, 2025
If your Omron Surge Protector circuit is cut off as soon as power is supplied, even though it wasn't designed for such a high current, the abnormal current tripping type might be set to 'instantaneous'. This setting detects abnormal current very quickly, potentially cutting off the circuit due to excessive current during equipment operation. You can either change the abnormal current tripping type from instantaneous to standard or raise the current tripping value. Alternatively, if there are a lot of devices connected to the output, which increases the operating current, use the S8M's startup sequence function to delay the connection of some devices.