1-14
H Main Circuit Terminals
Symbol Name Description
R/L1
Power supply input
til
3G3MV-A2j: 3-phase 200 to 230 V AC
S/L2
pp y p
terminals
p
3G3MV-ABj: Single-phase 200 to 240 V AC (See note 1.)
T/L3
gp ( )
3G3MV-A4j: 3-phase 380 to 460 V AC
U/T1
Motor output terminals 3-phase power supply output for driving motors. (See note 2.)
3G3MV A2j 3 h 200 t 230 V AC
V/T2
3G3MV-A2j: 3-phase 200 to 230 V AC
3G3MV
-
ABj:3
-
phase 200 to 240 V AC
W/T3
3G3MV
-
ABj:
3
-
phase
200
to
240
V
AC
3G3MV-A4j: 3-phase 380 to 460 V AC
B1
Braking Resistor
iil
Terminals for attaching an external Braking Resistor or a Braking
R i Ui(C d l di bki )
B2
g
connection terminals
gg g
Resistor Unit. (Connect to detect overvoltage during braking.)
+1
Connection terminals +1
and +2:
DC reactor connection
Connect the DC reactor for suppressing harmonics to terminals +1
and +2.
+2
DC
reactor connect
i
on
terminals
+1 and
:
When driving the Inverter with DC power, input the DC power to
terminals +1 and –.
(Terminal +1 is a positive terminal )
+1
and
:
DC power supply input
terminals
(Terminal
+1
is
a
positive
terminal
.
)
Ground terminal Be sure to ground the terminal under the following conditions.
3G3MV-A2j: Ground at a resistance of 100 or less.
3G3MV-ABj: Ground at a resistance of 100 or less.
3G3MV-A4j: Ground at a resistance of 10 or less. To conform
to EC Directives, connect to the neutral point of the power supply.
Note Be sure to connect the ground terminal directly to the
motor frame ground.
Note 1. Connect single-phase input to both the R/L1 terminal and the S/L2 terminal.
Note 2. The maximum voltage at the output side corresponds to the power supply voltage for Inverter
input.
Design Chapter 1