3-2
H Function Group 1 (n001 through n049)
Param-
eter
No.
Regis-
ter No.
(Hex)
Name Description Setting
range
Default
setting
Chan-
ges
during
opera-
tion
Memo
n001 0101 Parameter
write-prohibit
selection/pa-
rameter ini-
tialization
Used to prohibit parameters to be
written, sets parameters, or change
the monitor range of parameters.
Used to initialize parameters to
default settings.
0: Parameter n001 is set or dis-
played. Parameters from n002 to
n179 can be displayed only.
1: Parameters from n001 to n049
(function group 1) are set or dis-
played.
2: Parameters from n001 to n079
(function groups 1 and 2) are set
or displayed.
3: Parameters from n001 to n119
(function groups 1 through 3) are
set or displayed.
4: Parameters from n001 to n179
(function groups 1 through 4) are
set or displayed.
5: Operation commands can be ac-
cepted (n001 to n179 can be set)
while the red indicator is lit (i.e.,
while changing parameters or
switching between local and re-
mote.) (See note.)
6: Clears the error log.
8: Initializes parameters to default
settings in 2-wire sequence.
9: Initializes parameters to default
settings in 3-wire sequence.
10: For the USA, initializes parame-
ter in 2-wire sequence.
11: For the USA, initializes parame-
ter in 3-wire sequence.
Note If the parameter is set to 0 to
4, operation commands will
be ignored while the red indi-
cator is lit (refer to 2–1–2).
Normally, use the Inverter with
set values 0 to 4.
0 to 9 1 No
List of Parameters Chapter 3