3-12
H Function Group 2 (n050 through n079)
Param-
eter
No.
Reg-
ister
No.
(Hex)
Name Description Setting
range
Default
setting
Chan-
ges
during
opera-
tion
Memo
n050 0132 Multi-
function
input 1
Used to select the functions of multi-func-
tion input terminals S1 through S7.
1 to 33
(26 See
note )
1 No
i
npu
t
1
(Input ter-
minal S1)
Set
value
Function Description
no
t
e.
)
n051 0133 Multi-
function
input 2
(Input ter-
minal S2)
0 Forward/
Reverse
rotation
command
3-wire sequence
(to be set in n052
only)
By setting to 0,
the set values in
n050 and n051
are ignored and
the following set-
tings are forcibly
made.
1 to 33
(26 See
note.)
2 No
n052 0134 Multi-
function
input 3
(Input ter-
minal S3)
made
.
S1: RUN input
(RUN when ON)
S2: STOP input
(STOP when
OFF)
S3: Forward/Re-
verse rotation
command (OFF:
Forward; ON:
Reverse)
0 to 33
(26 See
note.)
3 No
n053 0135 Multi-
function
input 4
(Input ter-
minal S4)
1 Forward/
Stop
Forward rotation
command in
2-wire sequence.
(Forward rotation
with the signal
turned ON)
1 to 33
(26 See
note.)
5 No
n054 0136 Multi-
function
input 5
(Input ter-
minal S5)
2 Reverse/
Stop
Reverse rotation
command in
2-wire sequence
(Reversed with
the terminal
turned ON)
1 to 33
(26 See
note.)
6 No
n055 0137 Multi-
function
input 6
(Input ter-
i l S6)
3 External
fault (NO)
ON: External fault
(EFj detection:
j is a terminal
number)
1 to 33
(26 See
note.)
7 No
(p
minal S6)
4 External
fault (NC)
OFF: External
fault (EFj detec-
tion: j is a termi-
nal number)
Note Inverter overheating warning (setting value: 26) can be set for 5.5-kW and 7.5-kW Inverters only.
List of Parameters Chapter 3