H Function Group 3 (n080 through n0119)
Param-
eter
No.
Reg-
ister
No.
(Hex)
Name Description Set-
ting
range
Default
setting
Chan-
ges
during
opera-
tion
Memo
n080 0150 Carrier
frequency
selection
Used to set the carrier frequency.
Note The default setting does not need
any changes in normal operation.
1 to 4,
7 to 9
Varies
with the
capac-
ity.
No
n081 0151 Momen-
tary
power
interrup-
tion com-
pensation
Used to specify the processing that is per-
formed when a momentary power inter-
ruption occurs.
0: Inverter stops operating
1: Inverter continues operating if power
interruption is 0.5 s or less.
2: Inverter always continues operating.
5 to 100: Power interruption recovery tim-
er
Inverter restarts after the set value (5 to
100) 0.1 (second).
0 to 2,
5 to
100
0 No
n082 0152 Number
of fault
retries
Used set the number of times that reset
and restart are automatically attempted for
the Inverter when the Inverter has an
overvoltage fault or overcurrent fault.
0 to 10 0 No
List of Parameters Chapter 3