D Selecting RS-422/485 Termination Resistance
Termination resistance can be selected by setting pin 1 of the SW2 to ON. The default setting for the
pin is OFF.
Selects RS-422/485 termination resistance
Selects frequency reference input method
120- termination resistance (1/2 W)
Pin 1
D Selecting Frequency Reference Input Method
Frequency reference input
method
Pin 2 setting Frequency reference selection
(parameter n004)
Voltage input (default setting) V (OFF) Set value 2
Current input I (ON) Set value 3 or 4
Note Do not set pin 2 to ON for current input while voltage is being input, otherwise the resistor in the
input circuit may burn out.
D Frequency Reference Input by Pulse Train Input
The RP terminal can input or output a PLC or external pulse generator signal directly to the Inverter if
an analog signal is unable to provide an accurate reference.
This allows speed ratio and tracking operation between inverters.
Pulse train
Input
Output
Pulse train
Input
Design Chapter 1