n039 0127 Cooling fan
operation
Used to operate the Cooling Fan of
the Inverter while the Inverter is
turned ON or only while the Inverter
is in operation.
0: Rotates only while RUN com-
mand is input and for 1 minute
after Inverter stops operating
1: Rotates while Inverter is turned
ON
Note This parameter is available
only if the Inverter incorpo-
rates a Cooling Fan.
Note If the operation frequency of
the Inverter is low, the life of
the fan can be prolonged by
setting the parameter to 0.
0, 1 0 No
n040 0128 Motor rota-
tion direction
0: A forward command rotates the
motor counterclockwise when
viewed from the load.
1: A forward command rotates the
motor clockwise when viewed
from the load.
0, 1 0 No
n041 0129 Acceleration
time 3
Acceleration time: The time it takes
maximum frequency to go from 0%
to 100%.
0.0 to
6,000
10.0 Yes
n042 012A Deceleration
time 3
Deceleration time: The time it takes
maximum frequency to go from
100% to 0%.
10.0 Yes
n043 012B Acceleration
time 4
Note Actual acceleration/decelera-
tion time is calculated using
the following formula. Accel-
10.0 Yes
n044 012C Deceleration
time 4