Loading...
3-13
Param-
eter
No.
Reg-
ister
No.
(Hex)
Name Description Set-
ting
range
Default
setting
Chan-
ges
during
opera-
tion
Memo
n056 0138
Multi-
function
input 7
(
5 Fault reset ON: Fault reset (dis-
abled while RUN
command is input)
1 to
35,
(26
S
10 No
p
(Input ter-
minal S7)
6 Multi-step
speed ref-
erence 1
Signals to select fre-
quency references 1
through 16.
(
See
note.)
34, 35
7 Multi-step
speed ref-
erence 2
g
8 Multi-step
speed ref-
erence 3
9 Multi-step
speed ref-
erence 4
10 Inching
frequency
command
ON: Inching fre-
quency command
(taking precedence
over the multi-step
speed reference)
11 Accelera-
tion/decel-
eration
time
selection 1
See set value 27.
12 External
base block
command
(NO)
ON: Output turned
OFF
13 External
base block
command
(NC)
OFF: Output turned
OFF
14 Search
command
(Search-
ing starts
from maxi-
mum fre-
quency)
ON: Speed search
(Searching starts
from n011)
15 Search
command
(Search-
ing starts
from pre-
set fre-
quency)
ON: Speed search
List of Parameters Chapter 3