recent one)
Error
Error
generation
item
Note “1” means that the latest error is displayed. Press the
Increment Key to display the second latest error. A maxi-
mum of four errors can be displayed.
U-10 Software No. --- OMRON use only.
U-11 Output power W Monitors the output power of the Inverter. (See note 2.)
U-13 Accumulated
operating time
x10H Monitor the accumulated operating time in 10-second units.
(See note 3.)
U-15 Communications
error
--- Displays communications errors that occur during serial
communications (RS-422/RS-485). The errors that are
displayed have the same content as the serial
communications error at register number 003D Hex.
: Error
CRC error
: Normal
operation
Data length error
(Not used.)
Parity error
Overrun error
Communications time-over
(Not used.)
Framing error
U-16 PID feedback % Monitors the PID control feedback (Max. frequency: 100%)
U-17 PID input % Monitors the PID control input (Max. frequency: 100%)
U-18 PID output % Monitors the PID output (Max. frequency: 100%)
Note 1. The setting unit of the frequency reference and output frequency is determined by the set
value in n035. The default unit is Hz.
Note 2. The output power monitor is not displayed in vector control mode. “––––” is displayed instead.
Note 3. This function is provided for 200- and 400-V (5.5-/7.5-kW) Inverters only.
Preparing for Operation and Monitoring Chapter 2