3-26
Param-
eter
No.
MemoChan-
ges
during
opera-
tion
Default
setting
Set-
ting
range
DescriptionNameReg-
ister
No.
(Hex)
n092 015C Stall pre-
vention
during
decelera-
tion
Used to select a function to change the
deceleration time of the motor automati-
cally so that there will be no overvoltage
imposed on the motor during deceleration.
0: Stall prevention during deceleration
enabled
1: Stall prevention during deceleration dis-
abled
Note Be sure to set the parameter to 1
when the Braking Resistor Unit or a
braking resistor is used as an
option.
0, 1 0 No
n093 015D Stall pre-
vention
level dur-
ing accel-
eration
Used to select a function to stop the accel-
eration of the motor automatically for stall
prevention during acceleration.
Sets the level as a percentage based on
the rated current of the Inverter as 100%.
30 to
200
170 No
n094 015E Stall pre-
vention
level dur-
ing opera-
tion
Used to select a function to reduce the out-
put frequency of the Inverter automatically
for stall prevention during operation.
Sets the level as a percentage based on
the rated current of the Inverter as 100%.
30 to
200
160 No
n095 015F Fre-
quency
detection
level
Used to set the frequency to be detected.
Note The parameter n059 for multi-func-
tion output must be set for the out-
put of frequency detection levels 1
and 2.
0.00 to
400.0
0.00 No
n096 0160 Overtor-
que
detection
function
selection
1
Used to enable or disable overtorque
detection and select the processing
method after overtorque detection.
0: Overtorque detection disabled
1: Overtorque detection only when speed
coincides and operation continues
(issues alarm)
2: Overtorque detection only when speed
coincides and output turned OFF (for
protection)
3: Overtorque always detected and opera-
tion continues (issues alarm)
4: Overtorque always detected and output
turned OFF (for protection)
0 to 4 0 No
n097 0161 Overtor-
que
detection
function
selection
2
Select the item to detect overtorque.
0: Detected from output torque.
1: Detected from output current.
0, 1 0 No
List of Parameters Chapter 3