tage
as a percentage at each frequency
based on the rated motor voltage as
100%.
Note Normally, the default settings
do not need to be changed.
0 to
25
16 No
n161 01A1 Power detec-
tion width for
probe opera-
tion switching
Sets the detection width of power
that sets the Inverter into probe
operation.
Sets the width as a percentage
based on the power to be detected
as 100%.
Note Normally, the default setting
does not need to be changed.
Note The Inverter will operate with
a power detection width of
10% if the value is set to 0.
0 to
100
10 No
n162 01A2 Power detec-
tion filter con-
stant
Sets the filter time constant of the
power detection block of the Inverter
operating in probe operation.
Filter time constant (ms) = Set value
in n162 x 4 (ms)
Note Normally, the default setting
does not need to be changed.
Note The Inverter will operate with
a time constant of 20 ms if the
value is set to 0.
0 to
255
5 No
n163 01A3 PID output
gain
Sets the rate by which PID control
value is multiplied for PID control.
Note Normally, the default setting
does not need to be changed.
0.0 to
25.0
1.0 No
List of Parameters Chapter 3