4-6
Fault
display
Probable cause and remedyFault name and meaning
f07
Digital Operator fault (F07)
An error in the built-in control
circuit of the Digital Operator
has been detected.
The EEPROM of the Digital
Operator or the
analog-to-digital converter has
a failure.
The internal circuitry of the Digital Operator has a fault.
Turn the Digital Operator OFF and ON.
Replace the Digital Operator if the same fault occurs
again.
f21
Option Unit Self-diagnostic
fault (F21)
The Option Unit fails to start
initializing 2 seconds after
power is turned ON.
The Option Unit power may not be ON.
Check to see if the connectors are properly connected.
The Option Unit has malfunctioned.
Replace the Option Unit.
f22
Option Unit Model Code
fault (F22)
The Option Unit stopped while
trying to identify the Inverter
during communications
initialization.
The Option Unit may not be compatible with the Inverter.
Replace with the correct Option Unit.
Connectors may not be properly connected.
Check to see if the connectors are properly connected.
The Option Unit has malfunctioned.
Replace the Option Unit.
f23
Option Unit
Cross-diagnostic fault (F23)
Check to see if the connector is properly connected to the
casing.
Check to see if the frame ground wire for the Option Unit is
properly connected.
Take appropriate noise countermeasures.
%pr
Digital Operator connection
error (OPR)
The Inverter will detect this
error if n010 for Digital
Operator connection error
processing selection is set to
1.
The Digital Operator may not be mounted properly.
Turn OFF the Inverter, dismount and mount the Digital
Operator, and turn ON the Inverter.