1 Safety Instructions and General Warnings
6 I67E-EN V1000 Quick Start Guide
Precautions for CE Low Voltage Directive Compliance
This drive has been tested according to European standard EN61800-5-1, and it fully com-
plies with the Low Voltage Directive. The following conditions must be met to maintain
compliance when combining this drive with other devices:
Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3
in accordance with IEC664.
Ground the neutral point of the main power supply for 400 V Class drives.
Precautions for UL/cUL Standards Compliance
This drive is tested in accordance with UL standard UL508C and complies with UL require-
ments. The following conditions must be met to maintain compliance when using this drive
in combination with other equipment:
Do not install the drive to an area greater than pollution severity 2 (UL standard).
Use UL-listed copper wires (rated at 75° C) and closed-loop connectors or CSA-certified
ring connectors. For details refer to the instruction manual.
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local
codes for wiring. Use a class 2 (UL regulations) power supply for the control circuit termi-
nal. For details refer to the instruction manual.
This drive has undergone the UL short-circuit test, which certifies that during a short circuit
in the power supply the current flow will not rise above 30,000 amps maximum at 240 V for
200 V class drives and 480 V for 400 V class drives.
The drive internal motor overload protection is UL listed and in accordance with the NEC
and CEC. The setup can be done using the parameters L1-01/02. For details refer to the
instruction manual.
Precautions for Using the Safe Disable Function
The drive’s Safe Disable function is designed in accordance with the EN954-1, safety cate-
gory 3 and EN61508, SIL2. It can be utilized to perform a safe stop as defined by the
EN60204-1, stop category 0 (uncontrolled stop by removal of power). Refer to the instruction
manual for details about the application of this function.

Other manuals for Omron V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron V1000 and is the answer not in the manual?

Omron V1000 Specifications

General IconGeneral
Cooling MethodFan cooling
Enclosure RatingIP20
CommunicationModbus RTU
Output Power0.4-15kW
Output Frequency Range0 to 400 Hz
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
Supply Voltage200-240V AC (3-phase)