22 I67E-EN V1000 Quick Start Guide
6 Parameter Table
6 Parameter Table
This parameter table shows the most impor-
tant parameters. Default settings are bold
type. Refer to the instruction manual for a
complete list of parameters.
Par. Name Description
Initialization Parameters
A1-01
Access
Level
Selection
Selects which parameters are
accessible via the digital operator.
0:Operation only
1:User Parameters
2:Advanced Access Level
A1-02
Control
Method
Selection
Selects the Control Method of the
drive.
0: V/f Control
2: Open Loop Vector (OLV)
5: PM Open Loop Vector (PM)
Note: Not initialized with A1-03!
A1-03
Initialize
Parameters
Resets all parameters to default.
(returns to 0 after initialization)
No Initialize
1110: User Initialize (The user
must first set user parameter values
and then store them using parame-
ter o2-03)
2220: 2-Wire Initialization
3330: 3-Wire Initialization
Operation Mode Selection
b1-01
Frequency
Reference
Selection
0:Operator - d1- values
1:Analog input A1 or A2
2:Serial Com - RS-422/485
3:Option board
4:Pulse Input (Terminal RP)
b1-02
Run
Command
Selection
0:Operator - RUN and STOP keys
1:Terminals - Digital Inputs
2:Serial Com - RS-422/485
3:Option board connected
b1-03
Stopping
Method
Selection
Selects the stopping method when
the run command is removed.
0:Ramp to Stop
1:Coast to Stop
2:DC Injection Braking to Stop
3:Coast with Timer (a new run
command is ignored if received
before the timer expires)
b1-04
Reverse
Operation
Selection
0:Reverse enabled
1:Reverse prohibited
b1-14
Phase Order
Selection
Switches the output phase order.
0:Standard
1:Switch phase order
DC Injection Braking
b2-01
DC
Injection
Braking
Start Fre-
quency
Sets the frequency at which DC
Injection Braking starts when
Ramp to Stop (b1-03 = 0) is
selected. If b2-01< E1-09, DC
Injection Braking starts at E1-09.
b2-02
DC
Injection
Braking
Current
Sets the DC Injection Braking cur-
rent as a percentage of the drive
rated current.
In OLV the DC excitation current is
determined by E2-03.
b2-03
DC Inj.
Braking
Time/DC
Excitation
Time at
Start
Sets the time of DC Injection Brak-
ing at start in units of 0.01 seconds.
Disabled when set to 0.00 seconds.
b2-04
DC Inj.
Braking
Time at
Stop
Sets the DC Injection Braking time
at stop. Disabled when set to 0.00
seconds.
Acceleration/ Deceleration
C1-01
Accel
Time 1
Sets the acceleration time 1 from 0
to the max. output frequency.
C1-02
Decel
Time 1
Sets the deceleration time 2 from
the max. output frequency to 0.
Par. Name Description

Other manuals for Omron V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron V1000 and is the answer not in the manual?

Omron V1000 Specifications

General IconGeneral
Cooling MethodFan cooling
Enclosure RatingIP20
CommunicationModbus RTU
Output Power0.4-15kW
Output Frequency Range0 to 400 Hz
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
Supply Voltage200-240V AC (3-phase)