RFID System
User’s Manual
SECTION 5
V680 Commands
SECTION 5
Communications
OPERATION CONDITION SET (SE)
The OPERATION CONDITION SET command is used to set operation conditions for the Self Execu-
tion Mode. Always set the operation conditions in the following order from 1 to 5.
1. Clear the Operation Conditions
2. Set the Execution Command
Process code Always “20”.
Process code Always “00”.
Operation condition
parameter
“C1”: Sets an execution command for channel 1.
“C2”: Sets an execution command for channel 2.
Note: “C2” will result in an error (15) if specified for a One-channel Controller (V680-CA5D01-V2).
Also, if execution commands are not set for both channels 1 and 2 for a Two-channel Controller
(V680-CA5D02-V2), the output conditions cannot be set.
Execution command string Specifies the command to be executed, with the following restrictions.
1. Only Tag communications commands can be set: RD, WT, DF, or MD.
2. The communications designation must be RA or RI.
3. A maximum of 256 bytes can be written (for either ASCII or hexadecimal data)
The execution command will be set to “XX” if the execution command string is omitted.
Command
SE
2
2
*
CR
2
20
Command
code
Terminator
Process
code
Response
SE
2
2
*
CR
2
××
1
0
1
0
Command
code
Terminator End code
Resend
flag
Fixed
value
Command
SE
2
2
*
CR
Terminator
2
00
2
××
××
...
×
×
Execution Command
n
Command
code
Process
code
Operation
condition
parameter
Response
SE
2
2
*
CR
2
××
1
0
1
0
Command
code
Terminator End code
Resend
flag
Fixed
value