EasyManua.ls Logo

Omron VARISPEED V7

Omron VARISPEED V7
254 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Programming Features
123
Analog Input Level
Multi-function Analog Input Signal Selection (n078)
Frequency Reference Bias Setting (n079)
1. Auxiliary Frequency Reference
(n077=1)
2. Frequency Reference Gain
(n077=2)
3. Frequency Reference Bias (n077=3) 4. Output Voltage Bias (n077=4)
Constant
No.
Name Unit Setting Range Factory
Setting
n078 Multi-function
Analog Input Signal
Selection
- 0=Digital Operator terminal
(voltage: 0 to 10 V)
1=Digital Operator terminal
(current: 4 to 20 mA)
0
Constant
No.
Name Unit Setting Range Factory
Setting
n079 Frequency
Reference
Bias Setting
1 % 0 to 50
100 %/Max. Output Frequency
(n011)
10
100%
0%
0 V
(4 mA)
100%=Max. Output Frequency (n011)
10 V
(20 mA)
FREF2
2.00
1.00
0
0 V
(4 mA)
5 V 10 V
(20 mA)
FGAIN
n079
-n079
0 %
0 V
(4 mA)
5 V
10 V
(20 mA)
FBIAS
100 V
0 V
0 V
(4 mA)
10 V
(20 mA)
VBIAS
The VBIAS value to be added is
doubled for 400 V Class Inverters.

Table of Contents

Other manuals for Omron VARISPEED V7

Related product manuals