6 Programming Features
85
Frequency Offset Selection (n146)
An offset frequency (which can be set with a constant) can be added to
or subtracted from the frequency reference using multi-function inputs.
Constant
No.
Name Description Factory
Setting
n083 Jump Frequency 1
(Offset Frequency 1)
1st digit of n146 is 0 or 1:
Setting unit: 0.01 Hz
Setting range: 0.00 to
400.0 Hz
1st digit of n146 is 2:
Setting unit: 0.01%
Setting range: 0.00% to
100.0% (Percentage of Maxi-
mum Output Frequency)
0.00 Hz
n084 Jump Frequency 2
(Offset Frequency 2)
1st digit of n146 is 0 or 1:
Setting unit: 0.01 Hz
Setting range: 0.00 to
400.0 Hz
1st digit of n146 is 2:
Setting unit: 0.01%
Setting range: 0.00% to
100.0% (Percentage of Maxi-
mum Output Frequency)
0.00 Hz
n085 Jump Frequency 3
(Offset Frequency 3)
1st digit of n146 is 0 or 1:
Setting unit: 0.01 Hz
Setting range: 0.00 to
400.0 Hz
1st digit of n146 is 2:
Setting unit: 0.01%
Setting range: 0.00% to
100.0% (Percentage of Maxi-
mum Output Frequency)
0.00 Hz

Table of Contents

Other manuals for Omron VARISPEED V7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron VARISPEED V7 and is the answer not in the manual?

Omron VARISPEED V7 Specifications

General IconGeneral
BrandOmron
ModelVARISPEED V7
CategoryInverter
LanguageEnglish

Related product manuals