6 Programming Features
157
Error code
* Refer to the constants list for constants that can be changed during opera-
tion.
Error
Code
Contents
01H
Function code error
Function code from PLC is other than 03H, 08H, or 10H.
02H
Improper register number
No register numbers to be accessed have been registered.
Enter Command “0900H” (an exclusive-use register for write-in)
was read out.
03H
Improper quantity
The number of data items to be read or written-in is not in the
range between 1 and 16.
The number of data items in a message is not the value obtained
by multiplying the quantity by two in the write-in mode.
21H
Data setting error
A simple upper/lower limit error occurred with control data or con-
stant write-in.
A constant setting error occurred when a constant was written.
22H
Write-in mode error
Attempt to write in a constant from PLC was made during run-
ning.*
Attempt to write in an Enter Command from PLC was made dur-
ing running (n170=0).
Attempt to write in a constant from PLC was made during UV
occurrence.
Attempt to write in an Enter Command from PLC was made dur-
ing UV occurrence.
Attempt to write in a constant other than n001=12, 13 (constant
initialization) from PLC was made during “F04” occurrence.
Attempt to write in a constant from PLC was made while data
were being stored.
Attempt to write in data exclusive for read-out from PLC was
made.

Table of Contents

Other manuals for Omron VARISPEED V7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron VARISPEED V7 and is the answer not in the manual?

Omron VARISPEED V7 Specifications

General IconGeneral
BrandOmron
ModelVARISPEED V7
CategoryInverter
LanguageEnglish

Related product manuals