248
• For 400 V Class Inverters, always ground the supply neutral to con-
form to CE requirements.
EMC Directive
V7AZ Series Inverters satisfy testing for conformance to the EMC
Directive under the conditions described in European Standard
EN61800-3.
Installation Method
In order to ensure that the machinery or installation incorporating the
Inverter conforms to the EMC Directive, perform installation according
to the method below.
• Install a noise filter that conforms to European Standards on the input
side. (Refer to EMC Noise Filter on page 251.)
• Use a shielded line or metal piping for wiring between the Inverter
and Motor. Make the wiring as short as possible.
• For details of installation method, refer to Installation Manual (docu-
ment No. EZZ006543.)