146
List of Parameters Chapter 10
List of Parameter s
Para-
meter No.
(Register
No. (Hex))
Name Description Setting
range
Unit of
setting
Default
setting
Changes
during
operation
Refer-
ence
page
n01
(0101)
Parameter
write-
prohibit
selection/
parameter
initialization
Used to prohibit parameters to be written,
sets parameters, or change the monitor
range of parameters.
Used to initialize parameters to default
values.
0:Sets or monitors parameter n01.
Parameters n02 through n79 can be
monitored only.
1:Sets or monitors parameters n01
through n79.
6:Clears the error log.
8:Initializes parameters to default
values in 2-wire sequence.
9:Initializes parameters to default
values in 3-wire sequence.
0, 1, 6,
8, 9
1 1 No 5-2
n02
(0102)
Operation
command
selection
Used to select the input method for the RUN
and STOP commands in remote mode.
0:The RUN and STOP/RESET Keys on
the Digital Operator are enabled.
1:Multi-function inputs through the
control circuit terminals in 2- or 3-wire
sequence.
2:Operation commands via RS-422A/
485 communications are enabled.
Note The RUN command only through key
sequences on the Digital Operator is
acceptable in local mode.
0 to 2 1 0 No 5-7
n03
(0103)
Frequency
reference
selection
Used to set the input method for the
frequency reference in remote mode.
0:Digital Operator
1:Frequency reference 1 (n21)
2:Frequency reference control circuit
terminal (0 to 10 V)
3:Frequency reference control circuit
terminal (4 to 20 mA)
4:Frequency reference control circuit
terminal (0 to 20 mA)
6:Frequency reference via RS-422A/
485 communications
0 to 4,
6
1 0 No 5-8
n04
(0104)
Interrup-tion
mode
selection
Used to set the stopping method for use
when the STOP command is input.
0:Decelerates to stop in preset time.
1:Coasts to stop (with output shut off by
the STOP command)
0, 1 1 0 No 5-16
n05
(0105)
Reverse
rotation-
prohibit
selection
Used to select the operation with the reverse
command input.
0:Reverse enabled.
1:Reverse disabled.
0, 1 1 0 No 5-15
n06
(0106)
STOP/
RE-SET Key
function
selection
Used to select the stop method in remote
mode with n02 for operation mode selection
set to 1.
0:STOP/RESET Key of the Digital
Operator enabled.
1:STOP/RESET Key of the Digital
Operator disabled.
0, 1 1 0 No 5-7